Modified Phase Shifting of Leakage Current to Condition Monitoring of Metal Oxide Surge Arresters in Power System

Sirajudeen Mohamed Arshad1, Dr. Asanka S. Rodrigo2

  • 1University of Moratuwa, Sri Lanka
  • 2University of Moratuwa

Details

16:30 - 16:45 | Wed 30 May | Seminar Room | W.3.3-4

Session: Power Systems, Electrical Machines and High Voltage Engineering 1

Abstract

Metal Oxide Surge Arresters (MOSA) are proven to be reliable protective devices for power distribution and electrical transmission system. MOSA are subjected to electrical aging or degradation due to constant AC conduction or transient voltages. Leakage current measurements are used to monitor the degradation of surge arresters and the resistive leakage current is extracted from the total to determine the health of the surge arresters. As the resistive current increases, life of the surge arresters get decreases. In conventional method total leakage current is measured by using current shunts or current transformers along with the applied voltage which is very hard to measure in online condition. This paper develops an easy and accurate method to separate the resistive leakage current from the total leakage current without any voltage measurements by using a technique called Modified Phase Shifted Method (MPSM) and simulated in MATLAB which enables online monitoring system and easy to apply into a device.